New UPS monitor added to Xymonton

list Josh Luthman
Wed, 28 Jul 2010 14:41:06 -0400
Message-Id: <AANLkTi=user-34c0bc319c14@xymon.invalid>

I am having an issue with the graphs.  Is it possible the RRD was
created without supporting of two decimal places?

They are being referenced on their pages but the image does not show
up.  The RRD files exist and do have values:

-> rrdtool dump out-voltage.rrd |grep "name\|type\|last_ds"
                <name> 111111111</name>
                <type> GAUGE </type>
                <last_ds> 119.00 </last_ds>
                <name> 222222222</name>
                <type> GAUGE </type>
                <last_ds> 121.00 </last_ds>
                <name> 33333333333</name>
                <type> GAUGE </type>
                <last_ds> 120.00 </last_ds>


Josh Luthman
Office: XXX-XXX-XXXX
Direct: XXX-XXX-XXXX
XXXX Wayne St
Suite XXXX
Troy, OH XXXXX


On Wed, Jul 28, 2010 at 12:59 PM, Josh Luthman
<user-4c45a83f15cb@xymon.invalid> wrote:
That fixed it!  Thank you!

Josh Luthman
Office: XXX-XXX-XXXX
Direct: XXX-XXX-XXXX
XXXX Wayne St
Suite XXXX
Troy, OH XXXXX


On Wed, Jul 28, 2010 at 12:46 PM, Bill Arlofski <user-0b8af203a56e@xymon.invalid>
wrote:
On 07/28/10 12:29, Josh Luthman wrote:
 >Unless I am mistaken, the test I wrote will be set the status to
yellow if
the
UPS load is greater than or equal to $yellowtest (80%) and the status
will
be
set to red if the UPS load is eualto or greater than $redtest (80%).
While this may be your intention that is not what I'm seeing.  I am
getting
a red condition with these loads.

- UPS load % for apcxxxxxr01 apcyyyy01 apczzzzzzzzz01 on 127.0.0.1

apcxxxxxx01 : 51.00
apcyyyy01 : 11.00
apczzzzzzzz01 : 12.00

My yellow and red are 80 and 90 like you suggest (or at least your
default
is =)

-> cat ~myhobbituser/server/ext/xymon_nut_ups-load.sh|grep test
datatest="ups\.load:"
yellowtest="80"
redtest="90"

Josh Luthman

Ah... I see it...

Your UPS reports load % with two decimal points (51.00), mine reports %
load
with one (35.6)

So the logic in the script is correct, but the part where I was stripping
past
the decimal failed to take into account more than one decimal.

By only stripping the decimal and one numeral past it, the test is saying
"if
510 > 90 then set the status to red"


To fix it, change the line:

datanopoint=`echo "$data" | "$SED" -e 's/\.[0-9]//'`

to

datanopoint=`echo "$data" | "$SED" -e 's/\.[0-9]\{1,2\}//'`


P.S. I already made all the changes I mentioned in may last email and will
be
putting up the simplified versions possibly later today, including this
fix.


Thanks Josh

--
Bill Arlofski
Reverse Polarity, LLC